Every observation on an Electrical Installation Condition Report gets one of four codes. The codes are the inspector’s judgement on your installation, and they decide whether the report comes back satisfactory or unsatisfactory.
C1: Danger present
There is a risk of injury now, and immediate action is needed. Typical examples are exposed live parts and burnt or melted accessories. Most inspectors will make it safe or isolate it with your agreement before they leave, and tell you and the occupier. The permanent repair follows, within 28 days at the latest.
C2: Potentially dangerous
Not dangerous this minute, but it could become so if there were a fault. Missing main bonding, earth fault loop impedance that is too high, and no earth to metal light fittings are common C2s. For landlords in England, the remedial work is due within 28 days, or sooner if the report says so.
FI: Further investigation
Something needs looking into that couldn’t be resolved on the day, such as low insulation readings with no obvious cause, or circuits that can’t be traced. It has to be investigated within 28 days (or less if stated), and then whatever the investigation finds gets fixed.
C3: Improvement recommended
The installation doesn’t meet the current edition of BS 7671 at that point, but it isn’t unsafe. Missing circuit labels and older but sound wiring are typical. There is no legal deadline; it is worth planning in, for example alongside other work.
Satisfactory or unsatisfactory?
| Code | Meaning | Report overall | Landlord deadline (England) |
|---|---|---|---|
| C1 | Danger present | Unsatisfactory | Make safe now; repair within 28 days at the latest |
| C2 | Potentially dangerous | Unsatisfactory | 28 days, or less if the report says |
| FI | Further investigation | Unsatisfactory | Investigate within 28 days, then fix |
| C3 | Improvement recommended | Can still be satisfactory | None |
Any C1, C2 or FI makes the report unsatisfactory. C3s on their own don’t. If you have an unsatisfactory report, our post on the 28-day rule covers what has to happen next.
If a code surprises you
Ask which regulation it refers to. That is a fair question and any good inspector will answer it. Pressure to agree a large repair bill on the spot is a reason to pause: ask what each code is for and get a second quote. You can use any qualified electrician for the repairs.